Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-401a 11 2.3.11
GP Dimming Panels
GRAFIK Systems
®
Number Of
Circuits
Feed
Type
Maximum
Feed
Circuit
Breakers
1
15A
20 A
15A
20 A
15A
20 A
15A
3
20 A
3
GP3
GP4
1Ø, 2 W
1Ø, 3 W
3Ø, 4 W
Feed
Through
40 A
40 A
30 A
40 A
15A
20 A
20 A
20 A
Only standard panels listed. Consult Lutron for further options.
1
20/16A,15/12Acontinuousloadrating.
2
Measured current will not exceed continuous load rating due to voltage drop in the dimmer.
3
Breakerslocatedindistributionpanelsuppliedbyothers.
120 V Power
GP3/4 Mini Models
Number Of
Circuits
Circuit
Breakers
Feed
Type
Maximum
Feed
40 A
20 A
20 A
1Ø, 2 W
3Ø, 4 W
Feed
Through
GP3
GP4
20 A
20 A
20 A
3
277 V Power
Panel Branch Ratings
Maximum
DimmedHotLoad
2
1500W/VA
2000 W/VA
1500W/VA
2000 W/VA
1500W/VA
2000 W/VA
1500W/VA
2000 W/VA
Panel Branch Ratings
Maximum
DimmedHotLoad
2
4500W/VA
4500W/VA
4500W/VA
Power Equipment